APC Smart-UPS commands
vv
From some old notes, to not get lost...
| command | action |
| Y | enter “smart” mode |
| U | simulate power failure |
| D | start calibration cycle (works only if battery charge considered 100%) |
| W | perform self-test |
| E | set automatic self-test interval |
| B | query battery voltage |
| f | query battery charge level, % |
| j | query estimated runtime on battery |
| P | query load ratio (current load to unit’s rated max load) |
| C | query internal temperature |
| L | query input voltage |
| O | query output voltage |
| M | query max line voltage since unit reset |
| N | query min line voltage since unit reset |
| l (lowercase L) | set lower admissible line voltage |
| u | set upper admissible line voltage |
| e | set battery charge level prior to powering the load |
| r | set wakeup delay |
| s | set unit sensitivity (high/medium/low) |
| q | set “low battery” signaling level, in estimated runtime minutes |
| o | set lowest battery admissible voltage |
| p | set shutdown delay (time since UPS shutdown command) |
| n | queries some number (unit serial?) |
| G | queries cause of last transfer to batteries. returns:
|
| X | query self-test result. returns:
|